53% of internal area
HAIK ELECTRIC · ELECTRICAL CHARTS & REFERENCES
Conduit Fill Chart & Calculator
Compare EMT, IMC, and RMC. Check mixed conductor sizes, find a minimum trade size, and print your reference chart.
← Electrical Calculators · AC & DC Wire Color Codes Network Cable Color CodesBuild your conduit run
Conduit fill chart
Counts are conservative calculated capacities for identical THHN/THWN-2 conductors. The calculator uses occupied area without the optional same-size rounding allowance. A dash means no conductor of that size fits. Mixed sizes require the calculator above.
Allowable fill
31% of internal area
40% of internal area
60% of internal area
Method & reference sources
Fill = total conductor/cable area ÷ conduit internal area × 100. Custom circular area = π × outside diameter² ÷ 4. Standard conduit areas and THHN/THWN-2 conductor areas follow NEC Chapter 9, Tables 4 and 5; fill rules follow Table 1. Supported trade sizes: ½–4 inches. Minimum size means minimum within this supported range.
Fill check only. Ampacity adjustments, pulling difficulty, jam risk, bending limits, and local amendments require separate review. Verify the locally adopted NEC edition and actual cable construction before installation. A fill result does not determine ampacity.
- NFPA 70 — National Electrical Code
- Southwire conduit-fill reference calculator
- Wheatland IMC dimensions · Wheatland RMC dimensions
- Marathon EMT dimensions
Reference reviewed October 2026. Manufacturer nominal dimensions may differ slightly from rounded code-table areas.