200-amp service.
Every detail explained.

Overhead 120/240-volt, single-phase residential service: equipment, heights, clear working space and grounding.

2025 California Electrical Code · 2023 NEC foundation
Effective January 1, 2026 · Reviewed October 12, 2026

Explore the drawings
Conceptual realistic illustration of a residential overhead meter-main and service mast
AI-generated equipment illustration · conceptual, not an inspected installation

SEE HOW THE PARTS FIT TOGETHER

Three detailed installation drawings

Select a drawing to inspect its labels and measurement points at full size.

Annotated residential service illustration with meter height, working space, equipment labels and grounding inset
Annotated installation picture · limits and utility-dependent measurements are identified · Open full size ↗
Service mast, roof flashing and meter-main equipment
Service mast, roof flashing and meter-main equipment · Open full size ↗
Panel working clearances and handle-height limits
Panel working clearances and handle-height limits · Open full size ↗
Two-rod grounding design and communications bonding
Two-rod grounding design and communications bonding · Open full size ↗

MEASURE FROM THE CORRECT POINT

Heights, space and clearances

MeasurementRequirement / design statusMeasurement point
Working-space depth36″ minimum in this typical 120 V-to-ground caseEquipment face to the clear-space boundary
Working-space width30″ minimum or equipment width, whichever is greaterClear usable width; panel need not be centered
Working-space height6′6″ or equipment height, whichever is greater; review applicable exceptionsStanding surface to overhead obstruction
Breaker handle6′7″ maximum, ordinary accessible installationStanding surface to grip center in highest position
Door openingAt least 90°Equipment door / hinged panel opening
Meter centerUtility-specific; LADWP published example: 4′ to 6′3″Finished standing surface to meter-socket centerline
Panel bottomNo universal CEC minimum; utility / accessibility / equipment rules can governState the required measurement point in the project design
Rod spacing6′ minimum for multiple rodsBetween rods; no universal maximum spacing
Rod soil contactAt least 8′ in the normal vertical caseLength in contact with soil, not length above grade
Mast projection / bracingUtility + structural design + equipment requirementsRoof penetration / attachment / mast top as specified
Overhead wire clearancesSite-specific; verify CEC 230.24 and 230.9 plus utility rulesRoof, finished grade, driveway, windows, balconies and other surfaces
Gas equipment separationUtility / gas-provider-specificCheck meter, regulator vent and ignition-source rules

Do not use a single overhead-wire height for every location. Pedestrian areas, vehicle areas, roof slopes and openings have different conditions. Utility meter dimensions can change; confirm the current approved meter spot before construction.

NUMBERED MATERIALS REFERENCE

Equipment and installation details

01

200 A outdoor meter-main

Utility-approved meter socket and outdoor-rated enclosure, typically NEMA 3R. Verify bus rating, main disconnect, available fault current and equipment interrupting / short-circuit ratings.

02

2″ galvanized rigid metal conduit

Proposed service mast. Verify utility minimum, conductor fill, structural strength, wall supports, roof projection, bracing and attachment loading. Do not substitute EMT for a load-bearing mast.

03

2″ conduit hub

Listed weatherproof hub approved for the chosen enclosure. Confirm grounding and service-raceway bonding; a fitting must provide the required function, not merely fit the opening.

04

2″ service weatherhead

Listed service-entrance head. Show downward conductor exits and drip loops. Placement relative to the service attachment and required conductor tails follows CEC 230.54 and utility standards.

05

Adjustable service wire holder

Utility-approved service attachment and insulator. Attach to suitable structural support or an approved load-bearing mast; verify loading and fasteners.

06

Roof flashing

Flashing / boot compatible with the mast diameter, roof slope and roof material. Integrate with roofing according to manufacturer instructions.

07

Roof-flashing sealant / asphalt patch

Use roofing cement only when approved for that roofing and flashing. It supplements correctly installed flashing; it is not the primary waterproofing detail.

08

3/0 AWG copper service entrance

Proposed ungrounded conductors: 3/0 copper is 200 A at the 75°C table rating before applicable corrections and adjustments. Use wet-location-rated insulation such as THWN-2, compatible terminals and verified load calculations. Neutral size requires a separate calculation. Qualifying whole-dwelling services may use CEC 310.12; 3/0 copper is not a universal residential minimum.

09

Grounding electrode system

Connect all qualifying electrodes present, including applicable metal underground water piping and concrete-encased electrodes. Evaluate water-pipe and other required bonding. Two rods alone do not describe the complete system.

10

Two ⅝″ ground rods with at least 8′ soil contact

Show a two-rod design, minimum 6 ft apart, with at least 8 ft in contact with soil for the normal vertical installation. This above-grade connection illustration requires rods long enough to preserve that soil contact; protect rod tops, clamps and exposed conductors against physical damage. The continuous proposed #4 copper conductor runs from service equipment through rod 1 and rod 2 to the qualifying main metal water pipe. The communications bonding bar has its own separate connection from the service grounding terminal. Check rocky-ground exceptions. The second rod is not universally required when an allowed resistance test establishes 25 ohms or less; this guide proposes two rods without relying on that test.

11

#4 AWG copper grounding electrode conductor

Proposed design specification. Table 250.66 calls for #4 copper with 3/0 copper service conductors where the table applies. Rod-only connections have the 250.66(A) sizing limit; concrete-encased and other electrodes have separate provisions. Specify listed protection rather than generic “BX armor.” Bond ferrous protective raceways / armor as required at both ends.

12

Listed ground clamps

Suitable for conductor and electrode sizes; direct-burial rated where buried. Maintain required access or use permitted buried electrode connections. Protect exposed components from damage.

13

One-hole protective-cover strap

Listed strap matched to the selected cable or protective raceway. Support spacing and attachment follow the actual wiring method and product instructions; no universal “BX strap spacing” applies.

14

Intersystem bonding terminal

Listed accessible terminal for communications bonding, connected separately with the proposed #6 copper conductor from the bonded terminal at service equipment under CEC 250.94. It is not a separate isolated grounding system for low voltage.

A COMPLETE GROUNDING SYSTEM

Ground rods, bonding and the service neutral

At the service disconnect: provide the main bonding jumper according to the equipment listing and CEC requirements. Bond service raceways and enclosures. An exterior emergency disconnect is required for applicable one- and two-family dwelling installations under CEC 230.85; identify whether the selected device is service equipment or another permitted emergency-disconnect arrangement.

Downstream panels: keep neutral conductors isolated from equipment grounding conductors and enclosures. The service bonding point and grounding-electrode connection must follow the actual disconnect arrangement.

Armor is not a substitute for the grounding conductor. Use a properly sized copper grounding electrode conductor. If ferrous protection surrounds it, bond that protection as required by CEC 250.64(E). Select straps and fittings for the actual listed product.

Communications bonding: provide an accessible listed intersystem bonding terminal connected to the building service grounding system. Do not create an independent “low-voltage ground rod.”

FROM LOAD CALCULATION TO FINAL INSPECTION

Plan the upgrade in the right order

  1. Confirm capacity. Complete the dwelling load calculation, including relevant EV, HVAC and other planned loads; verify utility service capacity.
  2. Obtain the utility meter spot. Confirm overhead service acceptance, location, mast and attachment requirements, meter equipment and available fault current.
  3. Obtain permits and finalize the design. Confirm adopted code, local amendments, grounding electrodes, conductor sizes, raceway fill, outdoor ratings and roofing detail.
  4. Coordinate the outage and installation. Arrange utility disconnection, qualified installation, required inspections and the utility release / reconnection.
  5. Verify and document. Check manufacturer torque requirements, grounding and bonding, circuit identification, applicable protection and final inspection.

Discuss a panel upgrade with Haik Electric

Code and utility references

CEC: 110.3(B), 110.14(C), 110.26; 230.9, 230.24, 230.28, 230.54, 230.85; 240.24(A); 250.24, 250.50, 250.52(A)(5), 250.53(A), 250.64, 250.66, 250.92, 250.94; 310.12, Table 310.16 and Chapter 9 conductor-fill tables. Verify adopted text and applicable exceptions.

Utility rules supplement the adopted electrical code. This guide does not establish one statewide meter-height or mast-height standard.